HVAC Drive Programming Guide
21-58 Ext. 3 Feedback [Unit]
Range:
0.000
Ex-
[-999999.999 - 999999.999 Ex-
tPID3Unit*
tPID3Unit]
21-59 Ext. 3 Output [%]
Range:
0 %*
[0 - 100 %]
3.19.8 21-6* Closed-loop 3 PID
Configure the closed-loop 3 PID controller.
21-60 Ext. 3 Normal/Inverse Control
Option:
[0] *
Normal
[1]
Inverse
21-61 Ext. 3 Proportional Gain
Range:
0.01 N/A*
[0.00 - 10.00 N/A]
21-62 Ext. 3 Integral Time
Range:
10000.00
[0.01 - 10000.00 s]
s*
21-63 Ext. 3 Differentation Time
Range:
0.00 s*
[0.00 - 10.00 s]
21-64 Ext. 3 Dif. Gain Limit
Range:
5.0 N/A*
[1.0 - 50.0 N/A]
Function:
See par.21-18
Ext. 1 Feedback [Unit]
Function:
See par.21-19
Ext. 1 Output [%]
Function:
Ext. 1 Normal/Inverse Control
See par.21-20
Function:
Ext. 1 Proportional Gain
See par.21-21
Function:
Ext. 1 Integral Time
See par.21-22
Function:
Ext. 1 Differentation Time
See par.21-23
Function:
See par.21-24
Ext. 1 Dif. Gain Limit
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
for details.
for details.
for details.
for details.
for details.
for details.
for details.
3 Parameter Description
3
3-195