Main Menu - Load And Motor - Group - Danfoss VLT HVAC Series Programming Manual

Table of Contents

Advertisement

3 Parameter Description
0-83 Additional Non-Working Days
Array with 15 elements [0] - [14] displayed below parameter number in display. Press OK and step between elements by means of
on the LCP.
Range:
0 N/A*
[0 - 0 N/A]
3
0-89 Date and Time Readout
Range:
0 N/A*
[0 - 0 N/A]

3.3 Main Menu - Load and Motor - Group 1

3.3.1 General Settings, 1-0*
Define whether the adjustable frequency drive operates in open-loop or closed-loop.
1-00 Configuration Mode
Option:
[0] *
Open-loop
[3]
Closed-loop
NOTE!
This parameter cannot be changed when the motor is running.
NOTE!
When set for closed-loop, the commands reversing and start reversing will not reverse the direction of the motor.
3-18
Function:
Defines dates for additional working days that normally would be non-working days according to
Working Days
par.0-81
.
Function:
Displays the current date and time. The date and time is updated continuously.
The clock will not begin counting until a setting different from default has been made in par.
Set Date and Time
0-70
.
Function:
Motor speed is determined by applying a speed reference or by setting desired speed when in hand
mode.
Open-loop is also used if the adjustable frequency drive is part of a closed-loop control system based
on an external PID controller providing a speed reference signal as output.
Motor speed will be determined by a reference from the built-in PID controller varying the motor
speed as part of a closed-loop control process (e.g., constant pressure or flow). The PID controller
must be configured in par. 20-** or via the function set-ups accessed by pressing the [Quick Menu]
button.
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide