3 Parameter Description
3
Figure 3.3: Controlled ramp-down, longer line failure. Ramping down as long as the energy in the system allows for it, then the motor is
coasted.
Figure 3.4: Kinetic back-up, short line failure. Ride through as long as the energy in the system allows for it.
Figure 3.5: Kinetic back-up, longer line failure. The motor is coasted as soon as the energy in the system is too low.
14-11 Line Voltage at Line Fault
Range:
342. V*
[180 - 600 V]
3-136
Function:
This parameter defines the threshold voltage at which the selected function in par.14-10
ure
should be activated.
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide