3 Parameter Description
1-21 Motor Power [HP]
Range:
4.00 hp*
[0.09 - 3000.00 hp]
3
1-22 Motor Voltage
Range:
400. V*
[10. - 1000. V]
1-23 Motor Frequency
Range:
50. Hz*
[20 - 1000 Hz]
NOTE!
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range:
7.20 A*
[0.10 - 10000.00 A]
NOTE!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
1420. RPM* [100 - 60000 RPM]
NOTE!
This parameter cannot be changed while the motor is running.
3-20
Function:
Enter the nominal motor power in HP according to the motor nameplate data. The default value
corresponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in par.0-03
Motor Power [HP]
or par.1-21
is made invisible.
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Select the motor frequency value from the motor nameplate data.For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par.4-13
Maximum Reference
and par.3-03
to the 87 Hz application.
Function:
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection, etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide