3 Parameter Description
[40]
Out of ref range
[41]
Below reference low
[42]
Above reference high
[45]
Bus Ctrl
[46]
Bus Ctrl 1 if timeout
[47]
Bus Ctrl 0 if timeout
[55]
Pulse output
3
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL Digital Output A
[81]
SL Digital Output B
[82]
SL Digital Output C
[83]
SL Digital Output D
[84]
SL Digital Output E
3-62
See par. group 13-1*. If Comparator 0 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-1*. If Comparator 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
See par. group 13-4*. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
SL Controller Action
See par.13-52
. The input will go high whenever the Smart Logic Action [38]
Set dig. out. A high
is executed. The input will go low whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
See par.13-52
SL Controller Action
. The input will go high whenever the Smart Logic Action [39]
Set dig. out. Bhigh
is executed. The input will go low whenever the Smart Logic Action [33]
out. B low
is executed.
SL Controller Action
See par.13-52
. The input will go high whenever the Smart Logic Action [40]
Set dig. out. C high
is executed. The input will go low whenever the Smart Logic Action [34]
dig. out. C low
is executed.
See par.13-52
SL Controller Action
. The input will go high whenever the Smart Logic Action [41]
Set dig. out. D
high is executed. The input will go low whenever the Smart Logic Action [35]
dig. out. D low
is executed.
See par.13-52
SL Controller Action
. The input will go high whenever the Smart Logic Action [42]
Set dig. out. E high
is executed. The input will go low whenever the Smart Logic Action [36]
dig. out. E low
is executed.