3 Parameter Description
[19]
Freeze ref
[20]
Freeze output
3
[21]
Speed up
[22]
Slow
[23]
Set-up select bit 0
[24]
Set-up select bit 1
[32]
Pulse input
[34]
Ramp bit 0
[36]
Line failure inverse
[37]
Fire mode
[52]
Run Permissive
[53]
Hand start
[54]
Auto-start
[55]
DigiPot Increase
[56]
DigiPot Decrease
3-50
Freezes actual reference. The frozen reference is now the point of enable/condition for Speed up
and Slow to be used. If Speed up/down is used, the speed change always follows ramp 2 (par.
Ramp 2 Ramp-up Time
3-51
and par.3-52
3-03
Maximum Reference
. (For closed-loop, see par.20-14
Freezes actual motor frequency (Hz). The frozen motor frequency is now the point of enable/con-
dition for Speed up and Slow to be used. If Speed up/down is used, the speed change always follows
ramp 2 (par.3-51
Ramp 2 Ramp-up Time
par.1-23
Motor Frequency
.
NOTE!
When Freeze output is active, the adjustable frequency drive cannot be stopped
via a low 'start [13]' signal. Stop the adjustable frequency drive via a terminal
programmed for Coasting inverse [2] or Coast and reset, inverse [3].
For digital control of the up/down speed is desired (motor potentiometer). Activate this function by
selecting either Freeze reference or Freeze output. When Speed up is activated for less than 400
msec., the resulting reference will be increased by 0.1%. If Speed up is activated for more than 400
msec., the resulting reference will ramp according to Ramp 1 in par.3-41
Same as Speed up [21].
Selects one of the four set-ups. Set par. 0-10 to Multi Set-up.
Same as Set-up select bit 0 [23].
(Default Digital input 32)
Select Pulse input when using a pulse sequence as either reference or feedback. Scaling is done in
par. group 5-5*.
Select which ramp to use. Logic "0" will select ramp 1 while logic "1" will select ramp 2.
Select to activate function selected in par.14-10
situation.
A signal applied will put the adjustable frequency drive into fire mode and all other commands will
be disregarded. See 24-0*
Fire Mode
The input terminal, for which the Run permissive has been programmed must be logic "1" before a
start command can be accepted. Run permissive has a logic 'AND' function related to the terminal
which is programmed for
START
[8],
start running the motor, both conditions must be fulfilled. If Run Permissive is programmed on
multiple terminals, Run permissive needs only be logic '1' on one of the terminals for the function
to be carried out. The digital output signal for Run Request (
[20]) programmed in par. 5-3*, or par. 5-4*, will not be affected by Run Permissive.
A signal applied will put the adjustable frequency drive into hand mode as if button
LCP has been pressed and a normal stop command will be overridden. If disconnecting the signal,
the motor will stop. To make any other start commands valid, another digital input must be assigned
Auto-Start
to
and a signal applied to this. The
impact. The
Off
button on the LCP will override
On
or
Auto On
button to make
Hand Start
Start
Auto-Start
nor
, the motor will stop regardless of any normal Start command applied. If signal
Hand Start
Auto-Start
applied to both
and
on the LCP the motor will stop regardless of signals on
A signal applied will put the adjustable frequency drive into auto mode as if the LCP button
On
Hand Start
has been pressed. See also
Uses the input as an INCREASE signal to the Digital Potentiometer function described in parameter
group 3-9*
Uses the input as a DECREASE signal to the Digital Potentiometer function described in parameter
group 3-9*
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide
Ramp 2 Ramp-down Time
Maximum Reference/Feedb.
and par.3-52
Ramp 2 Ramp-down Time
Line Failure
. Line failure is active in the Logic "0"
.
Jog
[14] or
Freeze Output
[20], which means that in order to
Start
Jog
[8],
Hand On
Auto On
and
buttons on the LCP has no
Hand Start
and
Auto-Start
and
Auto Start
active again. If no signal on neither
Auto-Start
, the function will be
. If pressing the
Hand Start
Auto-Start
and
[53]
) in the range 0 - par.
).
) in the range 0 -
Ramp 1 Ramp-up Time
.
Freeze output
[14] or
Hand On
on the
. Press either the
Hand
Hand
Off
button
.
Auto