3 Parameter Description
23-12 Maintenance Time Base
Option:
[0] *
Disabled
[1]
Running Hours
3
[2]
Operating Hours
[3]
Date & Time
23-13 Maintenance Time Interval
Range:
1 h*
[1 - 2147483647 h]
23-14 Maintenance Date and Time
Range:
0 N/A*
[0 - 0 N/A]
3-218
Function:
Select the time base to be associated with the preventive maintenance event.
Disabled
[0] must be used when disabling the preventive maintenance event.
Running Hours
[1] is the number of hours the motor has been running. Running hours are not reset
Maintenance Time Interval
at power-on. The
Interval
.
Operating Hours
[2] is the number of hours the adjustable frequency drive has been running. Op-
erating hours are not reset at power-on. The
Maintenance Time Interval
23-13
.
Date & Time
[3] uses the internal clock. The date and time of the next maintenance occurrence
Maintenance Date and Time
must be specified in par.23-14
Function:
Set the interval associated with the current preventive maintenance event. This parameter is only
Running Hours
Operating Hours
used if
[1] or
Reset Maintenance Word
The timer is reset from par.23-15
Example:
A preventive maintenance event is set up for Monday at 8:00. par.23-12
Operating hours
Maintenance Time Interval
[2] and par.23-13
maintenance event will be indicated the following Monday at 8:00. If this maintenance event is not
reset until Tuesday at 9:00, the next occurrence will be the following Tuesday at 9:00.
Function:
Set the date and time for next maintenance occurrence if the preventive maintenance event is based
on date/time. The date format depends on the setting in par.0-71
Time Format
depends on the setting in par.0-72
NOTE!
The adjustable frequency drive has no back-up of the clock function and the set
date/time will reset to default (2000-01-01 00:00) after a power-down. In par.
Clock Fault
0-79
, it is possible to program for a warning in case the clock has not
been set properly, e.g., after a power-down.
The time set must be at least one hour from the current time!
NOTE!
When mounting an Analog I/O MCB109 option card, a battery back-up of the date
and time is included.
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Programming Guide
Maintenance Time
must be specified in par.23-13
Maintenance Time Interval
must be specified in par.
.
Maintenance Time Base
[2] is selected in par.23-12
.
Maintenance Time Base
is 7 x 24 hours=168 hours. The next
Date Format
while the time format
.
.
is