Additional Information On Sm 332; Ao 4 X 12 Bit - Siemens SIMATIC Manual

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

6.14.3

Additional information on SM 332; AO 4 x 12 Bit

Unused channels
To take unused output channels of SM 332; AO 4 x 12 Bit off power, set the "disabled"
argument at the "output type" parameter. Disabled channels do not have to be wired.
Line continuity check
SM 332; AO 4 x 12 Bit only performs a line continuity check at the current outputs.
In output ranges 0 mA to 20mA and ±20 mA, a "reliable" wire-break check is not possible for
output values of-20s to ±200 µA.
Short-circuit test
SM 332; AO 4 x 12 Bit only performs a short-circuit test at the voltage outputs.
Substitute values
You can configure the SM 332; AO 4 x 12 Bit for CPU STOP mode as follows: Outputs off
power, hold last value or set substitute values. The set substitute values must lie within the
output range.
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0)
Analog modules
467