Siemens SIMATIC Manual page 212

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Digital modules
3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0)
Technical specifications
Actuator selection data
Thermal current, continuous
Minimum load voltage / current
Residual current
Short circuit-proof to IEC 947-5-1
Switching capacity and useful life of contacts
with resistive load
Voltage
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
120 V DC
120 V DC
230 V AC
230 V AC
230 V AC
230 V AC
230 V AC
with inductive load
Voltage
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
120 V DC
230 V AC
230 V AC
230 V AC
230 V AC
230 V AC
212
max. 5 A
10 V /10 mA
1)
11.5 mA
2)
With circuit-breaker, characteristics B, for:
cos Φ 1.0: 600 A
cos Φ 0.5...0.7: 900 A
With 8 A Diazed fuse: 1000 A
Current
No. of switching cycles
(typical)
5.0 A
0.2 million
2.5 A
0.4 million
1.0 A
0.9 million
0.2 A
1.7 million
0.1 A
2 million
0.2 A
1.7 million
0.1 A
2 million
5.0 A
0.2 million
2.5 A
0.4 million
1.0 A
0.9 million
0.2 A
1.7 million
0.1 A
2 million
Current
No. of switching cycles
(typical)
5.0 A
0.1 million
2.5 A
0.25 million
1.0 A
0.5 million
0.2 A
1 million
0.1 A
1.2 million
0.1 A
1.2 million
5.0 A
0.1 million
2.5 A
0.25 million
1.0 A
0.5 million
0.2 A
1 million
0.1 A
1.2 million
Manual, 06/2017, A5E00105505-AJ
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents