Technical specifications
Wiring of the signal transmitters
for voltage measurement
for resistance measurement
with 2-wire connection
with 3-wire connection
with 4-wire connection
Characteristics linearization
for resistance thermometers
Technical unit of data formats
Actuator selection data
Output range (rated value)
Voltage
Load impedance (in the rated output range)
For voltage outputs
capacitive load
Voltage output
Short-circuit protection
Short-circuit current
Destruction limit against external voltages/currents
Voltage at outputs to MANA
Wiring of the actuators
for voltage output
2-wire connection
4-wire connection (measuring line)
* the error limits specified for the outputs are only valid when there is a high-ohm connection. In the entire load resistance
range, an additional error of <0.9 % can result.
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.17 Analog IO module SM 334; AI 4/AO 2 x 12 bit; (6ES7334-0KE00-0AB0)
supported
supported
supported
supported
programmable
Pt 100 (Climatic range)
degrees Centigrade
0 V to 10 V
min. 2.5 kΩ *
max. 1.0 µF
Yes
max. 30 mA
max. 15 V, continuous
using a 20-pin front connector
supported
not supported