3.30 Digital output module SM 322; DO 8 x DC 48-125 V/1.5 A; (6ES7322-1CF00-0AA0)
Technical specifications
Actuator selection data
Output voltage
"1" signal
Output current
"1" signal
Rated value
Permitted range
Permitted surge current
with "0" signal (residual current)
Output delay (resistive load)
"0" to "1" transition
"1" to "0" transition
Lamp load
Wiring two outputs in parallel
for redundant load control
for performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load
with lamp load
Internal limiting of the inductive shutdown voltage to
Short-circuit protection of the output
Threshold
Replacement fuses
Schurter
Wickman
Fuse holder
Wickman
Wiring of the actuators
1) Fuses on this module are only supplementary. External surge current protection (suitable
for tap circuits conforming to local regulations for electrical engineering) is required in the
supply lines of the load circuit.
2) Possible errors:
- no load voltage
- defective fuse
- output overload
3) If an overload condition is detected, the output is disabled for the duration of ca. 2.4 s.
186
min. L+ (-1.2 V)
1.5 A
10 mA to 1.5 A
max. 3 A for a duration of 10 ms
max. 0.5 mA
max. 2 ms
max. 15 ms
max. 15 W at 48 V
max. 40 W at 125 V
supported (only outputs of the same group)
not supported
supported
max. 25 Hz
max. 0.5 Hz
max. 10 Hz
typ. M (-1V)
3)
yes, electronic
typ. 4.4 A
Fuse 6.3 A/250 V, fast-blow, 5 x 20 mm