Analog modules
6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0)
6.8.2

Measurement types and measuring ranges

Introduction
SM 331; AI 2 x 12 Bit is equipped with a measuring range module. The measurement type
and range is configured at the "measuring range" parameter in
default "voltage" measurement type and "± 10 V range without having to program the
SM 331; AI 2 x 12 Bit in
Measuring range module
Change the position of the measuring range module to set the measurement type and range
(see the chapter
necessary settings are also available on the module's imprint. Mark the position of the
measuring range module on the front door (see figure).
Table 6- 21
Selected type of measurement
V: Voltage
TC-I: Thermocouple
(internal comparison) (thermal voltage meas-
urement)
TC-E: Thermocouples
(external comparison)
(thermal voltage measurement)
2DMU: Current (2-wire transducer)
4DMU: Current (4-wire transducer)
R-4L: Resistance
(4-wire connection)
376
STEP 7
.
Setting the measurement types and ranges of analog input channels
Measurement types and ranges
STEP 7
Measuring range
(type of sensor)
± 80 mV
± 250 mV
± 500 mV
± 1000 mV
± 2.5 V
± 5 V
1 V to 5 V
± 10 V
Type N [NiCrSi-NiSi]
Type E [NiCr-CuNi]
Type J [Fe-CuNi]
Type K [NiCr-Ni]
Type L [Fe-CuNi]
4 mA to 20 mA
± 3.2 mA
± 10 mA
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
150 Ω
300 Ω
600 Ω
Manual, 06/2017, A5E00105505-AJ
. You can use the
). The
Measuring range mod-
ule settings
A
B
A
D
C
A
S7-300 Module data