Representation of analog values in the current measuring ranges
Table 5- 8
Representation of analog values in the ±3.2 mA to ±20 mA current measuring ranges
System
Current measuring range
dec
hex
±20 mA
32767
7FFF
23.70 mA
32512
7F00
32511
7EFF
23.52 mA
27649
6C01
27648
6C00
20 mA
20736
5100
15 mA
1
1
723.4 nA
0
0
0 mA
-1
FFFF
-20736
AF00
-15 mA
-27648
9400
-20 mA
-27649
93FF
-32512
8100
-23.52 mA
-32513
80FF
-32768
8000
-23.70 mA
Table 5- 9
Representation of analog values in the 0 mA to 20 mA and 4 mA to 20 mA current measuring ranges
System
Current measuring range
dec
hex
0 mA to 20 mA
32767
7FFF
23.70 mA
32512
7F00
32511
7EFF
23.52 mA
27649
6C01
27648
6C00
20 mA
20736
5100
15 mA
1
1
723.4 nA
0
0
0 mA
-1
FFFF
-4864
ED00
-3.52 mA
-4865
ECFF
-32768
8000
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
5.1 Representation of the values for analog input channels
±10 mA
±3.2 mA
11.85 mA
3.79 mA
11.76 mA
3.76 mA
10 mA
3.2 mA
7.5 mA
2.4 mA
361.7 nA
115.7 nA
0 mA
0 mA
-7.5 mA
-2.4 mA
-10 mA
-3.2 mA
-11.76 mA
-3.76 mA
-11.85 mA
-3.79 mA
4 mA to 20 mA
22.96 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
1.185 mA
Principles of analog modules
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
265