Principles of analog modules
5.1 Representation of the values for analog input channels
Representation of the analog values of thermocouples type L
Table 5- 29
Representation of the analog values of thermocouples type L
Type L
Units
in °C
dec
hex
> 1150.0
32767
7FFF
1150.0
11500
2CEC
:
:
:
900.1
9001
2329
900.0
9000
2328
:
:
:
-200.0
-2000
F830
< -200.0
< -2000
< F830
Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong
type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...
... from F380
underflow and
H
outputs 8000
.
H
Representation of the analog values of thermocouples type N
Table 5- 30
Representation of the analog values of thermocouples type N
Type N
Units
in °C
dec
> 1550.0
32767
1550.0
15500
:
:
1300.1
13001
1300.0
13000
:
:
-270.0
-2700
< -270.0
< -2700
Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong
type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...
... from F0C4
underflow and
H
outputs 8000
.
H
276
Type L in °F Units
> 2102.0
H
2102.0
H
:
1652.2
H
1652.0
H
:
-328.0
H
< -328.0
H
... from EAC0
H
outputs 8000
H
Type N in
°F
hex
7FFF
> 2822.0
H
3C8C
2822.0
H
:
:
32C9
2372.2
H
32C8
2372.0
H
:
:
F574
-454.0
H
< F574
< -454.0
H
... from E5D4
H
outputs 8000
H
Type L in K
dec
hex
32767
7FFF
> 1423.2
H
21020
521C
1423.2
H
:
:
:
16522
408A
1173.3
H
16520
4088
1173.2
H
:
:
:
-3280
F330
73.2
H
< -3280
< F330
< 73.2
H
underflow and
... from FE2C
.
outputs 8000
Units
Type N in K Units
dec
hex
32767
7FFF
> 1823.2
H
28220
6E3C
1823.2
H
:
:
:
23722
5CAA
1573.3
H
23720
5CA8
1573.2
H
:
:
:
-4540
EE44
0
H
< -4540
<EE44
< 0
H
underflow and
... from FB70
.
outputs 8000
Units
Range
dec
hex
32767
7FFF
Overflow
H
14232
3798
Overshoot
H
range
:
:
11733
2DD5
H
11732
2DD4
Rated range
H
:
:
732
02DC
H
< 732
<02DC
Underflow
H
underflow and
H
.
H
Range
dec
hex
32767
7FFF
Overflow
H
18232
4738
Overshoot
H
range
:
:
15733
3D75
H
15732
3D74
Rated range
H
:
:
0
0000
H
< 0
< 0000
Underflow
H
underflow and
H
.
H
S7-300 Module data