Principles of analog modules
5.1 Representation of the values for analog input channels
Representation of the analog values of thermocouples type U
Table 5- 33
Representation of the analog values of thermocouples type U
Type U
Units
in °C
dec
> 850.0
32767
850.0
8500
:
:
600.1
6001
600.0
6000
:
:
-200.0
-2000
< -200.0
< -2000
Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong
type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...
... from F380
underflow and
H
outputs 8000
.
H
Representation of analog values for type TXK/XKL GOST thermocouple
Table 5- 34
Representation of analog values for type TXK/XKL GOST thermocouple
Type
Units
TXK/XKL
dec
in °C
> 1050.0
32767
1050.0
8500
:
:
800.1
8001
800.0
8000
:
:
0.0
0
:
:
-200.0
-2000
< -200.0
<-32768 <
278
Type U in
°F
hex
7FFF
> 1562.0
H
2134
1562.0
H
:
:
1771
1112.2
H
1770
1112.0
H
:
:
F830
-328.0
H
< F830
< -328.0
H
... from EAC0
H
outputs 8000
H
Type
Units
TXK/XKL
hex
dec
in °F
7FFF
> 1922.0
32767
H
2904
1922.0
19220
H
:
:
:
1F41
1472.1
14721
H
1F40
1472.0
14720
H
:
:
:
0000
32.0
320
H
:
:
:
F830
-328.0
-3280
H
< -328.0
<-32768 8000
F8000
H
Units
Type U in K Units
dec
hex
32767
7FFF
> 1123.2
H
15620
2738.0
1123.2
H
:
:
:
11122
2B72
873.2
H
11120
2B70
873.2
H
:
:
:
-3280
F330
73.2
H
< -3280
< F330
< 73.2
H
underflow and
... from FE2C
.
outputs 8000
Range
hex
7FFF
Overflow
H
4B14
Overshoot range
H
:
3981
H
3980
Rated range
H
:
0140
H
:
F330
H
Underflow
H
Range
dec
hex
32767
7FFF
Overflow
H
11232
2BE0
Overshoot
H
range
:
:
8732
221C
H
8732
221C
Rated range
H
:
:
732
02DC
H
< 732
<02DC
Underflow
H
underflow and
H
.
H
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ