Siemens SIMATIC Manual page 385

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Technical specifications
Temperature error (in relation to input range)
Resistance thermometer
Resistor
Linearity error (referenced to input range)
Resistance thermometer
Resistor
Repeat accuracy (in steady state at 25 °C, referenced to input
range)
Resistance thermometer
Resistor
Status, interrupts, diagnostics
Interrupts
Hardware interrupt
Diagnostics interrupt
Diagnostics function
Group error display
Diagnostic information can be read
Encoder selection data
Input range (rated values) input resistance
Resistance thermometer
Resistor
Permissible input voltage at voltage input (destruction limit)
Wiring of the signal transmitters
for resistance measurement
with 2-wire connection
with 3-wire connection
with 4-wire connection
Characteristic linearization
Resistance thermometer
Technical unit for temperature measurement
* The resistance test for compensation of the line resistances with a 3-wire connection is performed every 5 minutes.
** Wire break monitoring in 4-channel mode (hardware filter) is performed every 3 seconds.
*** The maximum line resistance with 3-wire encoder measurements for the RTD elements PT 10 and Cu 10 is 10 Ω. For
all other RTD elements, the maximum power resistance for 3-wire encoder measurements is 20 Ω.
**** In 4-channel mode, the converted value settles to 100% within 80 ms. The value determined in this process is
switched typically every 3.3 ms (max. 10 ms).
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.9 Analog input module SM 331; AI 8 x RTD; (6ES7331-7PF01-0AB0)
± 0.015 °C/K
± 0.005 %/K
± 0.2 °C
± 0.02 %
± 0.2 °C
± 0.01 %
Configurable (channels 0-7)
Configurable
Configurable
Red LED (group error)
possible
Pt 10, Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000,
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000, LG-Ni
1000, Cu 10, Cu 50, Cu 100 (standard and climatic)
150, 300, 600 Ω
35 V DC continuous 75 V DC for max. 1 s (duty
cycle 1 : 20)
with 40-pin front connector
possible
possible***
possible
Pt 10, Pt 50, Pt 100, Pt 200, Pt 500, Pt 1000,
Ni 100, Ni 120, Ni 200, Ni 500, Ni 1000, LG-Ni
1000, Cu 10, Cu 50, Cu 100 (standard and climatic)
Degrees Celsius / degrees Fahrenheit