6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0)
Technical specifications
Basic execution time of the module (independent of the number of
enabled channels)
in standard mode
in isochronous mode
Transient recovery time
with resistive load
with capacitive load
with inductive load
Interference suppression, error limits
Crosstalk between outputs
Operational limit (across entire temperature range, relative to measurement range end value in the selected output range)
Voltage output
Current output
Basic error limit (operational limit at 25 °C, relative to the measurement range end value in the selected output range)
Voltage output
± 10 V
0 V to 10 V
1 V to 5 V
Current output
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
Temperature error (relative to output range)
Voltage output
Current output
Linearity error (relative to output range)
Repeat accuracy (in transient state at 25°, relative to output range)
Output ripple; range 0 Hz to 50 kHz (relative to output range)
Status, interrupts, diagnostics
Interrupts
Diagnostic interrupt
Diagnostic functions
Group error display
Reading diagnostic information
Set substitute values
454
<800 μs
750 µs
0.2 ms
3.3 ms
0.5 ms (1 mH) / 3.3 ms (10 mH)
> 100 dB
±0.12%
±0.18%
±0.02%
±0.02%
±0.04%
±0.02%
±0.02%
±0.04%
± 0.0025%/K
± 0.004%/K
±0.004%
±0.002 %
±0.05 %
programmable
programmable
red LED (SF)
supported
yes, programmable
Manual, 06/2017, A5E00105505-AJ