Siemens SIMATIC Manual page 177

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

3.29 Digital output module SM 322; DO 8 x DC 24 V/ 0.5 A; with diagnostics interrupt; (6ES7322-8BF00-0AB0)
Technical specifications
Status, interrupts, diagnostics
Status display
Interrupts
Diagnostic interrupt
Diagnostic functions
Group error display
Channel error display (F)
Reading diagnostics data
Actuator selection data
Output voltage
"1" signal
without series diode
with series diode
Output current
"1" signal
Rated value
Permitted range
"0" signal (residual current)
Output delay (resistive load)
"0" to "1" transition
"1" to "0" transition
Load resistance range
Lamp load
Wiring two outputs in parallel
for redundant load control
for performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load to IEC 947-5-1, DC 13
with lamp load
Internal limiting of the inductive shutdown voltage to
Short-circuit protection of the output
Threshold
Wiring of the actuators
1) 5 mA to 0.6 A, with disabled wire-break monitoring
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
green LED per channel
programmable
programmable
red LED (SF)
red LED (F) per channel
supported
min. L + (- 0.8 V)
min. L+ (-1.6 V)
0.5 A
1)
10 mA to 0.6 A
max. 0.5 mA
max. 180 μs
max. 245 μs
48 Ω to 3 kΩ
max. 5 W
Only outputs with series diode and common refer-
ence potential
not supported
supported
1 binary input to IEC 61131, Type 2;
Type 1, with disabled wire-break monitoring
max. 100 Hz
max. 2 Hz
max. 10 Hz
typ. L + (-45 V)
yes, electronic
typ. 0.75 A to 1.5 A
using a 20-pin front connector
Digital modules
177

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents