Technical specifications
Voltages, currents, electrical potentials
Rated electronics supply voltage L+
•
Reverse polarity protection
Total current of outputs (per group)
•
horizontal mounting position up to 60°
•
vertical mounting position up to 40°
Electrical isolation
•
between channels and the backplane bus
•
between channels and the power supply to relays
•
between channels
in groups of
Maximum potential difference
•
Between M
and the power supply to relays and outputs
internal
•
Between outputs of different groups
Isolation test voltage
•
between M
and the power supply to relays
internal
•
between M
and the power supply to relays and outputs
internal
•
between outputs of different groups
Current consumption
•
from the backplane bus
•
from power supply L+
Power loss of the module
Status, interrupts, diagnostics
Status display
Interrupts
•
Diagnostic interrupt
Diagnostic functions
•
Group error display
•
Reading diagnostics information
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0)
24 V DC
yes
max. 5 A
max. 5 A
yes
yes
yes
1
250 V AC
500 V AC
500 V DC
1500 V AC
2000 V AC
max. 100 mA
max. 160 mA
typ. 3.5 W
green LED per channel
programmable
programmable
red LED (SF)
supported
Digital modules
211