Siemens SIMATIC Manual page 54

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Digital modules
3.1 Module overview
Table 3- 6
Digital output modules (continued)
Properties
Number of outputs
Output current
Rated load voltage
Suitable for...
Supports isochronous
mode
Programmable
diagnostics
Diagnostic interrupt
Substitute value output Yes
Special features
* This module is described in the ET 200M Signal Modules for Process Automation manual.
You can find the manual on the Internet
(http://support.automation.siemens.com/WW/view/en/7215812).
54
SM 322; DO 8 x
SM 322; DO 8 x
DC24V/0,5A with
DC48-125V/1,5A
diagnostics interrupt
(-8BF00-)
(-1CF00-)
8 DO; isolated in
8 DO; electrically iso-
groups of 8
lated in groups of 4,
with reverse polarity
protection
0.5 A
1.5 A
24 V DC
48 to 125 V DC
solenoid valves, DC contactors and signal
lamps
No
No
Yes
No
Yes
No
No
Redundant load con-
-
trol is supported
Module
SM 322; DO 8 x
AC120/230 V/2A
(-1FF01-)
8 DO; isolated in
groups of 4
2 A
120/230 V AC
AC solenoid valves, contactors, motor starters,
FHP motors and signal lamps.
No
no
no
no
Fuse blown display.
Replaceable fuse for
each group
Manual, 06/2017, A5E00105505-AJ
SM 322;DO 8 x
AC120/230 V/ 2A
ISOL
(-5FF00-)
8 DO; isolated in
groups of 1
2 A
120/230 V AC
No
yes
yes
yes
-
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents