Programmable Parameters - Siemens SIMATIC Manual

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Analog modules
6.15 Analog output module SM 332; AO 2 x 12 Bit; (6ES7332-5HB01-0AB0)
6.15.2

Programmable parameters

Introduction
For general information on programming analog modules, refer to the chapter Programming
analog modules (Page 294).
The table below provides an overview of configurable parameters, including defaults:
Table 6- 39
Overview of the parameters of SM 332; AO 2 x 12 Bit
Parameter
Enable
Diagnostic interrupt
Diagnostics
Group diagnostics
Edition
Output type
Output range
Reaction to CPU STOP ASS
Assigning parameters to channels
The parameters can be set separately at each output channel of SM 332; AO 2 x 12 Bit. You
can assign separate parameters to each output channel.
Assign the parameters you set at the SFCs in the user program to the channel groups. Each
output channel of SM 332; AO 2 x 12 Bit is thus assigned to a channel group, i.e. output
channel 0 > channel group 0, for example.
Note
The output may carry invalid interim values if you modify output ranges while SM 332; AO
2 x 12 bit is in RUN.
See also
Diagnostic messages of analog output modules (Page 296)
474
Range of values
Yes/no
Yes/no
disabled
Voltage
Current
See chapter Output ranges for SM 332;
AO 2 x 12 Bit (Page 473)
Outputs zero cur-
rent/voltage
HLV
Hold last value
SSV
Set substitute value
Default
Parameter
type
No
Dynamic
No
Static
V
dynamic
± 10 V
ASS
dynamic
Manual, 06/2017, A5E00105505-AJ
Scope
Module
Channel
Channel
Channel
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents