Principles of analog modules
5.1 Representation of the values for analog input channels
Representation of the analog values of Ni x00 Standard resistance thermometers
Table 5- 14
Representation of the analog values of Ni100, 120, 200, 500, 1000 and
LG-Ni 1000 resistance thermometers
Ni x00
Units
Standard
dec
in °C (1 digit
= 0.1°C)
> 295.0
32767
295.0
2950
:
:
250.1
2501
250.0
2500
:
:
-60.0
-600
-60.1
-601
:
:
-105.0
-1050
< -105.0
-32768
Representation of the analog values of Ni x00 climate resistance thermometers
The following table shows the analog values for the resistance thermometer Nix00 Climatic
for all analog input modules.
Exceptions:
● Analog input module AI 8x12-bit; 6ES7331-7KF02-0AB0
● Analog input module AI 2x12-bit; 6ES7331-7KB02-0AB0
There is no overrange for these analog input modules. Overflow begins at 240 °C and is
encoded with 7FFF
268
Ni x00
Units
Standard in
hex
dec
°F (1 digit =
0.1 °F)
7FFF
> 563.0
32767
H
B86
563.0
5630
H
:
:
:
9C5
482.1
4821
H
9C4
482.0
4820
H
:
:
:
FDA8
-76.0
-760
H
FDA7
-76.1
-761
H
:
:
:
FBE6
-157.0
-1570
H
8000
< -157.0
-32768
H
.
H
Ni x00
standard
hex
in K (1 digit
= 0.1 K)
7FFF
> 568.2
H
15FE
568.2
H
:
:
12D5
523.3
H
12D4
523.2
H
:
:
FD08
213.2
H
FD07
213.1
H
:
:
F9DE
168.2
H
8000
< 168.2
H
Units
Range
dec
hex
32767
7FFF
Overflow
H
5682
1632
Overshoot
H
range
:
:
5233
1471
H
5232
1470
Rated range
H
:
:
2132
854
H
2131
853
Undershoot
H
range
:
:
1682
692
H
32768
8000
Underflow
H
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents