Siemens SIMATIC Manual page 142

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Digital modules
3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0)
Technical specifications
Isolation test voltage
Current consumption
from the backplane bus
from load voltage L1 (no-load)
Power loss of the module
Status, interrupts, diagnostics
Status display
Interrupts
Diagnostic functions
Group error display
Actuator selection data
Output voltage
"1" signal
Output current
"1" signal
Rated value
Permitted range
Maximum inrush current (per group)
"0" signal (residual current)
Output delay (resistive load)
"0" to "1" transition
"1" to "0" transition
Blocking voltage
zero transition
Size of the motor starter
Lamp load
Wiring two outputs in parallel
for redundant load control
for performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load to IEC 947-5-1, AC 15
with lamp load
Short-circuit protection of the output
Wiring of the actuators
*Requires two front connectors of the appropriate version
142
4000 VDC
max. 190 mA
max. 10 mA
typ. 25 W
green LED per channel
no
yes
red LED (SF)
min. L1 (-0.8 V)
1 A
10 mA to 1 A
10 A (for two AC cycles)
max. 2 mA
1 AC cycle
1 AC cycle
max. 60 V
max. size 4 to NEMA
max. 50 W
supported (only outputs of the same group)
not supported
supported
max. 10 Hz
max. 0.5 Hz
1 Hz
no
using a 20-pin* front connector
Manual, 06/2017, A5E00105505-AJ
S7-300 Module data

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents