Digital modules
3.22 Digital output module SM 322; DO 32 x AC 120/230 V/1 A; (6ES7322-1FL00-0AA0)
Technical specifications
Isolation test voltage
Current consumption
•
from the backplane bus
•
from load voltage L1 (no-load)
Power loss of the module
Status, interrupts, diagnostics
Status display
Interrupts
Diagnostic functions
•
Group error display
Actuator selection data
Output voltage
•
"1" signal
Output current
•
"1" signal
Rated value
Permitted range
Maximum inrush current (per group)
•
"0" signal (residual current)
Output delay (resistive load)
•
"0" to "1" transition
•
"1" to "0" transition
Blocking voltage
zero transition
Size of the motor starter
Lamp load
Wiring two outputs in parallel
•
for redundant load control
•
for performance increase
Control of a digital input
Switching frequency
•
with resistive load
•
with inductive load to IEC 947-5-1, AC 15
•
with lamp load
Short-circuit protection of the output
Wiring of the actuators
*Requires two front connectors of the appropriate version
142
4000 VDC
max. 190 mA
max. 10 mA
typ. 25 W
green LED per channel
no
yes
red LED (SF)
min. L1 (-0.8 V)
1 A
10 mA to 1 A
10 A (for two AC cycles)
max. 2 mA
1 AC cycle
1 AC cycle
max. 60 V
max. size 4 to NEMA
max. 50 W
supported (only outputs of the same group)
not supported
supported
max. 10 Hz
max. 0.5 Hz
1 Hz
no
using a 20-pin* front connector
Manual, 06/2017, A5E00105505-AJ