Parameter sets of signal modules
A.7 Parameters of analog input module SM 331; AI 8 x RTD
Interference frequency suppression at SM 331; AI 8 x RTD
The table below contains the frequency codes to be entered at byte 1 of data record 128
(see the previous figure.) The 50 Hz, 60 Hz and 400 Hz only apply to 8channel software filter
mode. The 50 Hz, 60 Hz and 400 Hz settings only apply to 4- and 8-channel hardware filter
mode.
Table A- 11
Interference suppression coding of SM 331; AI 8 x RTD
Interference frequency suppression
400 Hz
60 Hz
50 Hz
50/60/400 Hz
Measurement types and measuring ranges of SM 331; AI 8 x RTD
The table below shows all measurement types and measuring ranges of the module,
including their codes. Enter these codes at the corresponding bytes of data record 128 (see
the figure
Table A- 12
Measuring range codes of SM 331; AI 8 x RTD
Measurement type
disabled
Resistance (4-wire connection)
Resistance (3-wire connection)
544
Data record 1 for the parameters of analog input modules
Code
2#0000
2#0100
2#0101
Measuring range
disabled
150 Ω
300 Ω
600 Ω
150 Ω
300 Ω
600 Ω
Code
2#00
2#01
2#10
2#11
).
Code
2#0000
2#0010
2#0100
2#0110
2#0010
2#0100
2#0110