Analog modules
6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0)
6.5.2
Programmable parameters
Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 294).
Parameter
Table 6- 15
Overview of parameters for SM 331; AI 8 x 14 Bit High Speed
Parameters
Enable
•
Diagnostics interrupt
•
Process interrupt when limit
exceeded
Fast Mode (can only be set if the
331-7HF01 is included for isoch-
ronous operation in the DP slave
properties)
Process interrupt trigger
•
High limit
•
Low limit
Diagnostics
•
Group diagnostics
Measurement
•
Measurement type
•
Measuring range
•
Noise suppression
336
Range of values
yes/no
yes/no
yes/no
May be restricted by the measuring range.
from 32511 to - 32512
from - 32512 to 32511
yes/no
disabled
Voltage V
4DMU current (4-wire transducer)
2DMU current (2-wire transducer)
Measurement types and
See the table
ranges
none; 400 Hz; 60 Hz; 50 Hz
Default
Parameter
type
no
dynamic
no
no
static
-
dynamic
no
static
V
dynamic
± 10 V
50 Hz
Manual, 06/2017, A5E00105505-AJ
Scope
Module
Module
Channel
Channel
group
Channel or
channel
group
S7-300 Module data