Analog modules
6.13 Analog output module SM 332; AO 4 x 16 bit; isochrone; (6ES7332-7ND02-0AB0)
6.13.1
SM 332; AO 4 x 16 Bit - Output ranges
Introduction
You can configure the outputs for operation as voltage or current outputs, or disable these.
You program the outputs at the "output type" parameter in
The output type "Voltage" and output range "± 10 V" are set by default at the module. You
can always use this combination of output type and range without having to program the
SM 332; AO 4 x 16 Bit in
Output ranges
You program the output ranges for voltage and current outputs in
Table 6- 34
Selected type of output
Voltage
Current
456
STEP 7
.
Output ranges SM 332; AO 4 x 16 Bit
STEP 7
.
STEP 7
Output range
1 V to 5 V
0 V to 10 V
± 10 V
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
Manual, 06/2017, A5E00105505-AJ
.