3.26 Digital output module SM 322; DO 16 x UC 24/48 V; (6ES7322-5GH00-0AB0)
Dimensions and weight
Actuator selection data
Output voltage
"1" signal
Output current
Rated inrush current (per group) with "1" signal
"0" signal (residual current)
Output delay (resistive load)
"0" to "1" transition
"1" to "0" transition
External fuse for relay outputs
Lamp load
Internal parallel wiring of 2 outputs
for redundant load control
for performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load to IEC 947-5-1; DC 12 AC/12
with lamp load
Wiring of the actuators
* Outputs must be protected by a 250 V fast-blow fuse (recommended fuses: Wickman
194-1100 1.1 A and Littlefuse 0217-800 V 800 mA.)
When mounted in a hazardous area to National Electric Code (NEC), always remove the
fuse when the module is outside of the potentially explosive atmosphere, and use a suitable
tool.
Configuration in RUN
Special considerations must be given if you use the Configuration in RUN function.
SF LED is lit:
Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or
module), although diagnostics are no longer pending and the module is operating correctly.
Solution:
● Only change the configuration when no diagnostics are pending for the module or
● Pulling and plugging the module.
164
min. L+ (-0.25 V)
0.5 A max. 1.5 A (max. 50 ms)
max. 10 μA
max. 6 ms
max. 3 ms
Fuse, I
2 t
:1 A
2
s, fast-blow fuse*
max. 2.5 W
Varistor, 85 V
supported
not supported
supported
max. 10 Hz
max. 0.5 Hz
max. 0.5 Hz
using a 40pin front connector
Manual, 06/2017, A5E00105505-AJ
S7-300 Module data