Technical specifications
Operating mode
Integration/conversion time/resolution (per channel)
programmable
Basic conversion time in ms
additional conversion time for wire-break monitoring in ms
Resolution (including overshoot range)
Interference frequency suppression at interference frequen-
cy f1 in Hz
Measured value smoothing
Basic execution time of the module (all channels enabled)
Interference frequency suppression, error limits
Interference frequency suppression at f = n (f1 1%), (f1 = interference frequency) n = 1.2, etc.
Common mode interference (V
Series-mode interference (peak interference value < rated
input range)
Crosstalk between inputs
Operational limit (across temperature range, relative to the measurement range end value of the input range) (0 to 60 °C)
Note: This limit does not cover the temperature-error comparison points.
Thermocouple
Type T
-200 °C to
-230 °C to
Type U
-150 °C to
-200 °C to
Type E
-200 °C to
-230 °C to
Type J
-150 °C to
-210 °C to
Type L
-150 °C to
-200 °C to
Type K
-150 °C to
-220 °C to
Type N
-150 °C to
-220 °C to
Type R
+100 °C to
-50 °C to
Type S
+100 °C to
-50 °C to
Type B ****
+800 °C to
+200 °C
Type C
+100 °C to
0 °C
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.10 Analog input module SM 331; AI 8 x TC; (6ES7331-7PF11-0AB0)
< 60 V AC)
CM
4-channel mode (hardware filter)
Yes
3.3 ms *****
93 *
16 bits (including sign)
400/60/50
none/weak/medium/strong
10 ms ******
> 100 dB
> 90 dB **
> 100 dB
+400 °C
-200 °C
+600 °C
-150 °C
+1000 °C
-200 °C
+1200 °C
-150 °C
+900 °C
-150 °C
+1372 °C
-150 °C
+1300 °C
-150 °C
+1769 °C
+100 °C
+1769 °C
+100 °C
+1820 °C
+800 °C
+2315 °C
+100 °C
Analog modules
± 0.7 °C
± 1.5 °C
± 0.9 °C
± 1.2 °C
± 1.2 °C
± 1.5 °C
± 1.4 °C
± 1.7 °C
± 1.5 °C
± 1.8 °C
± 2.1 °C
± 2.9 °C
± 2.2 °C
± 3.0 °C
± 1.5 °C
± 1.8 °C
± 1.7 °C
± 2.0 °C
± 2.3 °C
± 2.5 °C
± 2.3 °C
± 2.5 °C