Siemens SIMATIC Manual page 138

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Digital modules
3.21 Digital output module SM 322; DO 32 x DC 24 V/ 0.5 A; (6ES7322-1BL00-0AA0)
Technical specifications
Actuator selection data
Output voltage
"1" signal
Output current
"1" signal
Rated value
Permitted range
"0" signal (residual current)
Output delay (resistive load)
"0" to "1" transition
"1" to "0" transition
Load resistance range
Lamp load
Wiring two outputs in parallel
For redundant load control
For performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load to IEC 947-5-1, DC 13
with lamp load
Internal limiting of the inductive shutdown voltage to
Short-circuit protection of the output
Threshold
Wiring of the actuators
138
min. L + (- 0.8 V)
0.5 A
5 mA to 0.6 A
max. 0.5 mA
max. 100 μs
max. 500 μs
48 Ω to 4 kΩ
max. 5 W
supported (only outputs of the same group)
Not supported
Supported
max. 100 Hz
max. 0.5 Hz
max. 10 Hz
typ. L + (-53 V)
yes, electronic
typ. 1 A
using a 40-pin front connector