Analog modules
6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0)
Technical specifications
Interference frequency suppression and error limits
Interference frequency suppression at f = n (f1 1%), (f1 = interference frequency); n= 1, 2, ...
Common mode interference (CMV < 50 V)
Series mode interference (peak value of interference < rated
input range)
Crosstalk between inputs
Operational limit (across entire temperature range, relative to
measurement range end value in the selected input range)
Voltage input
Current input
Basic error limit (operational limit at 25 °C, relative to measurement range end value in the selected input range)
Voltage input
Current input
Temperature error (relative to input range)
Linearity error (relative to input range)
Repeat accuracy (in transient state at 25 °C, relative to input
range)
Status, interrupts, diagnostics
Interrupts
Limit interrupt
Diagnostic interrupt
Diagnostic functions
Group error display
Reading diagnostic information
Encoder selection data
Input ranges (rated values) / input impedance
Voltage
Current
Maximum voltage at voltage input (destruction limit)
Maximum current at current input (destruction limit)
Wiring of the signal transmitters
for voltage measurement
for current measurement
as 2-wire transducer
as 4-wire transducer
312
> 100 dB
> 90 dB
> 100 dB
C
= 0 / CMV = ±50 V
MV
±0.1% / ± 0.7%
±0.3% / ± 0.9%
±0.05%
±0.05%
± 0.005%/K
±0.03%
±0.025%
programmable
Channels 0 and 2
programmable
programmable
red LED (SF)
supported
± 5 V
1 V to 5 V
± 10 V
0 mA to 20 mA
± 20 mA
4 mA to 20 mA
max. 50 V, continuous
max. 32 mA
using a 40pin front connector
supported
possible, with separate transducer supply
supported
/ 2 MΩ
/ 2 MΩ
/ 2 MΩ
/ 250 Ω
/ 250 Ω
/ 250 Ω