Siemens SIMATIC Manual page 280

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Principles of analog modules
5.2 Representation of analog values for analog output channels
Representation of analog values in the voltage output ranges
Table 5- 37
Representation of analog values in the ±10 V output range
System
dec
118,5149 %
32767
32512
117,589 %
32511
27649
100 %
27648
75 %
20736
0,003617 %
1
0 %
0
-1
-75 %
-20736
-100 %
-27648
-27649
-117,593 %
-32512
-32513
-118,519 %
-32768
Table 5- 38
Representation of analog values in the 0 V to 10 V and 1 V to 5 V output ranges
System
dec
118,5149 %
32767
32512
117,589 %
32511
27649
100 %
27648
75 %
20736
0,003617 %
1
0 %
0
-1
-25 %
-6912
-6913
-117,593 %
-32512
-32513
-118,519 %
-32768
280
Voltage output range
hex
±10 V
7FFF
0.00 V
7F00
7EFF
11.76 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
-361.7 µV
AF00
-7.5 V
9400
-10 V
93FF
8100
-11.76 V
80FF
8000
0.00 V
Voltage output range
hex
0 V to 10 V
7FFF
0.00 V
7F00
7EFF
11.76 V
6C01
6C00
10 V
5100
7.5 V
1
361.7 µV
0
0 V
FFFF
E500
E4FF
8100
80FF
8000
0.00 V
Overflow, off power
Overshoot range
Rated range
Undershoot range
Underflow, at zero voltage and current
1 V to 5 V
0.00 V
Overflow, off power
5.70 V
Overshoot range
5 V
Rated range
3.75 V
1 V +144.7 µV
1 V
Undershoot range
0 V
Not supported. Output value limited to
0 V.
Underflow, at zero voltage and cur-
rent
0.00 V
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents