Siemens SIMATIC Manual page 464

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Analog modules
6.14 Analog output module SM 332; AO 4 x 12 Bit; (6ES7332-5HD01-0AB0)
Technical specifications
Interference frequency suppression, error limits
Crosstalk between outputs
Operational limit (across entire temperature range, relative to measurement range end value in the selected output range)
Voltage output
Current output
Basic error limit (operational limit at 25 °C, relative to the measurement range end value in the selected output range)
Voltage output
Current output
Temperature error (relative to output range)
Linearity error (relative to output range)
Repeat accuracy (in settled state at 25 °C, relative to output range)
Output ripple; range 0 Hz to 50 kHz (relative to output range)
Status, interrupts, diagnostics
Interrupts
Diagnostic interrupt
Diagnostic functions
Group fault display
Reading diagnostic information
Setting substitute values
Actuator selection data
Output ranges (rated values)
Voltage
Current
Load impedance (in the rated range of the output)
For voltage outputs
Capacitive load
For current outputs
at CMV < 1 V
inductive load
Voltage output
Short-circuit protection
Short-circuit current
Current output
noload voltage
464
> 40 dB
± 0.5 %
± 0.6 %
± 0.4 %
± 0.5 %
± 0.002 %/K
± 0.05 %
± 0.05 %
± 0.05 %
Programmable
programmable
Red LED (SF)
Supported
Yes, programmable
± 10 V
0 V to 10 V
1 V to 5 V
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
Min. 1 kΩ
Max. 1 µF
max. 500 Ω
max. 600 Ω
max. 10 mH
Yes
max. 25 mA
max. 18 V
Manual, 06/2017, A5E00105505-AJ