Technical specifications
Maximum voltage at voltage input (destruction limit)
Maximum current at current input (destruction limit)
Wiring of the signal transmitters
for voltage measurement
for current measurement
as 2-ire transducer
as 4-wire transducer
For thermoresistor/resistance measurement
With 2-wire connection
With 3-wire connection
With 4-wire connection
Load of the 2-wire transducer
Characteristics linearization
for thermocouples
for resistance thermometers
Temperature compensation
Internal temperature compensation
External temperature compensation with compensating
box
Compensation for 0 °C reference junction temperature
Technical unit of temperature measurement
See also
Causes of error and troubleshooting at analog input modules (Page 297)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0)
max. 20 V continuous; 75 V for the duration of max. 1 s
(duty factor 1:20)
40 mA
using a 20-pin front connector
supported
supported
supported
Supported, cable resistances are not compensated
Supported, cable resistances are not compensated
Supported, cable resistances are compensated
max. 820 Ω
programmable
Types E, N, J, K, L
Pt 100 (Standard and Klima range)
Ni 100 (Standard and Klima range)
programmable
supported
supported
supported
degrees Centigrade