Siemens SIMATIC Manual page 361

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Technical specifications
Status, interrupts, diagnostics
Interrupts
Limit interrupt
Diagnostic interrupt
Diagnostic functions
Group error display
Reading diagnostics information
Encoder selection data
Input ranges (rated values) / input impedance
Voltage
Current
Resistance
Thermocouples
Resistance thermometer
Maximum voltage at voltage input (destruction limit)
Maximum current at current input (destruction limit)
Wiring of the signal transmitters
for voltage measurement
for current measurement
as 2-wire transducer
as 4-wire transducer
For thermoresistor/resistance measurement
with 2-wire connection
with 3-wire connection
with 4-wire connection
Load of the 2-wire transducer
Characteristics linearization
for thermocouples
for resistance thermometers
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0)
programmable
Channels 0 and 2
programmable
programmable
red LED (SF)
supported
± 80 mV
± 250 mV
± 500 mV
± 1,000 mV
± 2.5 V
± 5 V
1 V to 5 V
± 10 V
± 3.2 mA
± 10 mA
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
150 Ω
300 Ω
600 Ω
Types E, N, J, K, L
Pt 100, Ni 100
max. 20 V, continuous
75 V for the duration of max. 1 s (duty factor 1:20)
40 mA
using a 20-pin front connector
supported
supported
supported
Supported, cable resistances are not compensated
Supported, cable resistances are not compensated
Supported, cable resistances are compensated
max. 820 Ω
programmable
Types E, N, J, K, L
Pt 100 (Standard and Klima range)
Ni 100 (Standard and Klima range)
Analog modules
10 MΩ
10 MΩ
10 MΩ
10 MΩ
100 kΩ
100 kΩ
100 kΩ
100 kΩ
25 Ω
25 Ω
25 Ω
25 Ω
25 Ω
10 MΩ
10 MΩ
10 MΩ
10 MΩ
10 MΩ
361