A.12 Parameters of analog output modules
Output types and output ranges
The table below lists all output types/ranges of the analog output modules, including their
codes. Enter these codes at bytes 2 to 5 in data record 1 (refer to the previous figure.)
Table A- 31
Output range codes of analog output modules
Output type
disabled
Voltage
Current
See also
Analog modules (Page 300)
576
Code
Output range
2#0000
disabled
2#0001
1 V to 5 V
0 V to 10 V
± 10 V
2#0010
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
Code
2#0000
2#0111
2#1000
2#1001
2#0010
2#0011
2#0100
S7-300 Module data