Siemens SIMATIC Manual page 373

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Technical specifications
Generation of analog values
Measuring principle
Integration/conversion time/resolution (per channel)
programmable
Integration time in ms
Basic conversion time, including the integration time in ms
Additional conversion time for resistance measurement, in ms
or
additional conversion time for wire-break monitoring in ms
or
additional conversion time for resistance measurements and
wire-break monitoring in ms
Resolution in bits (including overshoot range)
Interference frequency suppression at interference fre-
quency f1 in Hz
Basic execution time of the module in ms (all channels
enabled)
Measured value smoothing
Interference frequency suppression, error limits
Interference frequency suppression at f = n (f1 ± 1%), (f1 = interference frequency) n=1.2...
Common mode interference (V
Seriesmode interference (peak interference value < rated
input range)
Crosstalk between inputs
Operational limit (across entire temperature range, relative to the measurement range end value of the selected input
range)
Voltage input
Current input
Resistance
Thermocouple
Resistance thermometer
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0)
< 2.5 V)
CM
Integrating
Yes
2
2.5
16
/
3
3
17
1
1
10
10
16
16
9 bits
12 bits
400
60
6
34
none
> 70 dB
> 40 dB
> 50 dB
80 mV
250 mV to 1,000 mV
2.5 V to 10 V
3.2 mA to 20 mA
150 Ω; 300 Ω; 600 Ω
Types E, N, J, K, L
Pt 100/Ni 100
Pt 100 Klima
Analog modules
20
100
22
102
1
1
10
10
16
16
12 bits
14 bits
50
10
44
204
± 1 %
± 0.6 %
± 0.8 %
± 0.7 %
± 0. 7 %
± 1. 1 %
± 0. 7 %
± 0. 8 %
373