Table 4-3.
Subcombiner wire
sizing
and torque values
Fuse Block
Maximum Wire Size
Required Torque
Terminal
Maximum
Temp.
Amperage
Rating
600
Al/Cu
500kcmil-#4
58 Nm ( 43
ft-lb)
75°C
400
Al/Cu 350kcmil-#4
58 Nm (
43
ft-lb)
75°C
200
Al/Cu
350kcmil-#6
42 Nm
(31
·ft-lb)
75°C
100
Al/Cu
#2/0-6
14 Nm
(10
ft-lb)
75°C
Direct
to bus
bar
No wire
size
limit.
Must
use grade 8
54 Nm (
40
ft-lb)
90°C
3/8"
hardware.
CONNECTING TO THE PV ARRAYS
Lt,
DANGER:
Before proceeding with the DC
wiring,
confirm that the
PV
array has been
disconnected from the inverter using the external DC disconnect.