6-20. Modbus inverter operating status register values (Continued)
Description
Hex
Value
Decimal Value
Modbus register number= 42101
Rese1ved
6
6
Rese1ved
7
7
Rese1ved
8
8
Fault
state
9
9
Initialization
state
A
10
Disabled
state
B
11
Latching fault
state
c
12
Cool
down state
D
13
The following table
contains
the bitmap
infonnation for
the PVM
status register
. The
response values
for
this command
are
shown
in the table as
both
hex and
decimal
values.
When multiple
codes
are
set,
the resulting
status word value will be a sum of
the individual
code
values.
Table 6-2
1.
PVM status register status code values
Description
Hex
Value
Decimal Value
Notes
Modbus register number = 42005
OK
0
0
Rebooting
1
1
Inve1ter
2
2
Results in return
value
communication
fault
of zero for reads
of
data registers listed in
Table 6-18
on
page
6-25
.
Web
post fault
4
4
DNS
se1ver
fault
8
8
Real
time clock
enor
10
16
The
batte1y is
dead
or
cannot synchronize
with the network time
se1ver.
Wrong
20
32
Incompatible
or
communications
inconect revision
of
fumware
communications
fumware.
Modbus
address
enor
40
64
Failed reading the
Modbus
address
switches.
6-28
Data Monitoring and Controls
570-1001793-0SB