9-2. Electrical Specifications - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced Energy
Note
the following limits:
Accuracy
limit
of voltage
and
energy
production measurements: ±
5%
Accuracy
limit
of frequency
measurement:± 0.1 Hz
Table
9-2. Electrical specifications
Description
Specification
AC
Characte1i
stics
Continuous
AC
power
AE
75TX
:
75
kW
AE
l
OOTX:
100 kW
Gdd
type
Three
phase,
four wire wye (not compatible
with delta
service)
Nominal AC voltage (V AC)
208 V AC
models:
208 wye
480
V AC
models: 480
wye
600 V AC
models:
600 wye
Maximum output
fault cwTent
and
AE
75TX:
322 Aims at 208 V AC, 72.2
ms
duration
Note
1
AE
75TX:
111
Aims at 600 V AC, 72.2
ms
AE
l
OOTX:
322 A
nns at
208
VAC,
72.2
ms
AE
l
OOTX:
111
A
nns at
600
VAC,
72.2
ms
Maximum
utility backf
eed
cwTent
AE
75TX:
902 A
AE
1
OOTX:
902 A
AC
maximum
continuous
cunent
AE
75TX:
208 V AC: 208 A
AE
75TX:
480
VAC: 91 A
AE
75TX:
600 V AC: 73 A
AE
l
OOTX:
208
VAC:
278 A
AE
l
OOTX:
480
VAC:
120
A
AE
l
OOTX:
600 VAC
:
96 A
CEC
efficiency
AE
75TX:
208 VAC: 95
.5%
AE
75TX:
480
VAC: 95
.5%
AE
75TX:
600 V AC:
96.0%
AE
l
OOTX:
208 VAC
:
95.5%
AE
l
OOTX:
480
VAC:
96.0%
AE
l
OOTX:
600
VAC:
96.0%
Peak efficiency
AE
75TX:
>96%
AE
l
OOTX:
>96%
Frequency range
59.3 Hz to
60.5
Hz
AC voltage
range
set
points (default)
(-
12% to
+
10%)