Installing The Modbus Rs-485 Cable - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced
Energy
I
Communications
Interface PCB
-----------------------------------+---------------------------------,
Shield
I
.
-
Shield
I
.
-
I
I
00 0
00 0
0
------------- ------- ------- --------------- -------
\
c
RS-485
Network
to
Field
(Inverter or Gateway)
0
------ ------------
4660
/
Modbus
slave
I
I
L
RS-485
Network to
Field
(Inverter
or Gateway)
Figure
6-8.
Connecting dual Modbus slave pott terminal blocks
Installing the Modbus RS-485 Cable
6-10
MODBUS RS-485 WIRING REQUIREMENTS
The
Modbus
RTU connections are made using shielded,
insulated,
18-24 gauge
twisted-pair
communication
cable
that has a characteristic impedance
of
120
Q.
If
the
RS-485 network
will
not pass
through
any high voltage
(> 300 V)
areas,
then
300 V
rated cable may be
used
in the low
voltage
data monitoling compartment
of
the
inve1ter. Check with
your
local
inspector
or
project engineer if
you
need assistance in
detennining this requirement.
Some appropliate 300
V
data cables
include:
Belden
3
105A
(1P22
A WG shielded)
Belden
3082A
(1P
15
AWG
+
1P
18
AWG shielded)
Belden
7897A
(1P
15
AWG
+
1P
18
AWG shielded)
is
an example
ofa 600 V
rated
cable that may
also
be
used;
others exist
as well.
TO INSTALL THE MODBUS RS-485 CABLE
Lt
DANGER:
Risk of electrical
shock.
High voltages are present in the inverter cabinet.
Both AC and DC disconnects must be in the OFF position when working on
the unit. Wait five minutes to discharge high voltage before opening the front
panels
of
the inverter.
Data Monitoring
and
Controls
570-1001793-0SB