Figure 6-5.
Daisy chain layout for
RS-485
network: option
A
SINGlEPOINT
CABlE5"EL.0
EARlH GROUND
~
+
"'
0
0
ISOLATED,
SELN'OWERED
MASTEROE\'ICE
Figure 6-6.
Daisy chain layout for
RS-485
network: option
B
r----l-d---+-t-+-1--'<::f-~-'<::f--"f"+-ir+++--1::7---------'o>---++++-"'<7-~
1
i2
4648
Figure 6-7.
Daisy chain layout for
RS-485
network: option C
Important
When multiple devices are
wired to
the
network,
the network
shield
must be
te1minated to
eai1h ground at one
point on the
network,
typically
at the
beginning or the end.
For
device
connections,
the
shield
must
be
rewired to
provide
a continuous
shield
and
isolated
from ground.
Modbus Wiring for the Slave Port
The communications interface includes two
Modbus
slave
po11 tenninal
blocks.
The
two
Modbus
slave
po11 te1minal
blocks can be
used in
an
in-and-out
configuration
for
daisy-chain networking. The
two
te1minal blocks ai·e electiically bonded
on
the PCB.
Therefore,
it
does
not matter
which one
is
used or
the
order
in
which
they ai·e
connected.
The following illustration
provides
an example of
how
the two
te1minal
blocks
can
be used.
570-1001793-0SB
Data Monitoring
and Controls
6-9