6-8.
Format for Read Holding Register command (Continued)
Command Information
Command Layout
Command
number
03
First
register
MSB
xx
First
register LSB
xx
Data
MSB
xx
DataLSB
xx
CRCLSB
xx
CRCMSB
xx
Table
6-9. Response format for Read Holding Register command
Response Information
Response Layout
Modbus
address
nn
Command number
03
Number of
bytes
of data
n
First register
MSB
xx
First
register
LSB
xx
Second register
MSB
xx
Second register
LSB
xx
Nth
register MSB
xx
Nth
register
LSB
xx
CRCLSB
xx
CRCMSB
xx
The Write Single
Register
colll1Iland
is
used
to write data
to
a
register.
Table
6-10. Format for Write Single Register command
Command Information
Command Layout
Modbus
address
nn
Command number
06
First register
MSB
xx
First register
LSB
xx
Nth
register MSB
xx
Nth
register
LSB
xx
CRCLSB
xx