Advanced Energy AE 75TX Installation And Operation Manual page 123

Table of Contents

Advertisement

Advanced Energy®
AE
?STX and
AE
1 OOTX Inverters
Table 8-3.
Drive
(DR
V) faults
Display Screen
Display Screen Text
Description
Hexadecimal
Value
0001
DRIVE A LOW
Diive protection
fault,
phase
A
low
0002
DRIVE A
HIGH
D1ive protection
fault,
phase A high
0004
DRIVE
B
LOW
Drive protection
fault,
phase B low
0008
DRIVE
BIDGH
Drive protection
fault,
phase B high
0010
DRIVE CLOW
Drive protection
fault,
phase C low
0020
DRIVEC
HIGH
Drive protection
fault,
phase C high
0040
HW OVER CURRENT
A
Peak
over-cunent,
phase
A
0080
HW OVER CURRENT B
Peak
over-cunent,
phase B
0100
HW OVER CURRENT
C
Peak
over-cunent,
phase C
0200
RMS
OVERCURRENT
A
RMS over-cwTent, phase
A
0400
RMS
OVERCURRENT B
RMS over-cwTent, phase B
0800
RMS
OVERCURRENT
C
RMS over-cwTent, phase
C
1000
DC OVERVOLTAGE
DC
volts
over range
2000
DC UNDERVOLTAGE
DC
volts
under range
Voltage Faults
The following table lists the
voltage
faults,
including
V AC
sense, VDC,
and the
power
supply.
Contact
AE
Solar
Energy
Technical Suppo1t for
assistance
in resolving
a voltage
fault.
Table 8-4.
Voltage (VL T) faults
Display Screen
Display Screen Text
Description
Hexadecimal
Value
0001
VAC
OVER PEAK
A
Peak AC
voltage
high,
phase A
0002
VAC
OVER PEAK B
Peak AC
voltage
high,
phase B
0004
VAC
OVER
PEAK C
Peak AC
voltage
high,
phase
C
0008
PLL FAULT
Control PLL
fault
0010
AC
UNBALANCED FAULT
AC
voltages
unbalanced
0020
DC
OVER
VOLTAGE
DC
voltage
high
0040
POWER
SUPPLY PS
5
V
power
supply
fault
0080
POWER
SUPPLY P15
15
V
power
supply
fault
570-1001793-0SB