Utility Interconnect Specifications - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced Energy®
AE
?STX and
AE
1 OOTX Inverters
Table
9-2 Electrical specifications (Continued)
Description
Specification
AC operating range
208 V AC models: 183 V AC to 288 V AC
480 V AC models: 423
V
AC to 528 V
AC
600 V AC models: 528 V AC to 660 V
AC
Power factor at full power
>
0.99
Total
ha1monic
disto1tion
<
3%
Standby losses
AE 75TX:
<
42 W
AE
l
OOTX:
<
42 W
DC Characte1istics
DC
sho1
t circuit cunent rating
675A
Maximum operating input cunent
AE 75TX: 267 A
AE
l
OOTX:
356 A
MPPT
range
Note 2
295
V
to 595
V
Maximum voltage at open circuit
600
V
0
c
Sta1
tup voltage
330
V
Staitup power
AE 75TX: 1800 W
AE
1
OOTX:
1800 W
Note 1
Info1mation also known
as
the maximum fault cunent contribution.
Note
2
At unity power factor and
nominal
AC
voltage.
Utility Interconnect Specifications
Table 9-3.
Utility interconnect voltage and frequency trip limits and times
Voltage and Frequency Trip Limits and Times
The default trip
limits
and
times
meet
ULl
741 anti-islanding
requirements.
Voltage nip limit field adjustment range
as
a percentage of nominal:
-22%
to
+
18%
Accessible range of
frequency
trip
times:
0. 16
s
to 300 s
Accessible range
oflow frequency setting (Hz)
:
Adjustable
low
n·ip 57.5 to 59.8 Hz
High nip fixed at 60.5 Hz
(The accuracy liinit of time measurement
is
±
0.1
s .)
208 V AC Configurations
Factory Setting
Standard Tlip
T1ip Time
Condition
(VAC)
R
ange (V AC)
Time (seconds)
Range
570-1001793-0SB
Specifications
A-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae 100tx

Table of Contents