Using The Infrared Inspection Ports - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced Energy
Table 8-7.
System
(SYS) faults (Continued)
Display
Display Screen Text
Description
Action
Screen Hex
Value
0002
AC
CONTACTOR
AC
contactor fault
0004
DC
CONTACTOR
DC
contactor fault
0008
WDTIMER
Watchdog fault
0010
CPU
LOAD
CPU load fault
Contact AE Solar
0020
RESTART LIMIT
Too
many fault resta1ts
Energy
Technical
0040
CONFIGURATION
Configuration fault
Suppo1t for
AC
cunent
imbalance
service.
0080
CURRENT
IMBALANCE
0100
AC VOLTAGE
SENSE
No AC voltage detected
0400
THERMAL SWITCH
OPEN Thennal
switch open
0800
DISCONNECT
OPEN
Disconnect
open
1000
DCMISWIRE
DC mis-wired
for
Check the
DC
configured grounding
wiring.
USING THE INFRARED INSPECTION PORTS
The
infrared inspection
po1ts in the upper
cabinet
can be
used
to inspect the isolation
transfo1mer
and
inductors
.
To Use the Infrared Inspection Ports
8-12
1.
Open the air intake hood
by loosing
the three latches on the front edge.
Lift
the
hood to the open
position.
2. Remove the two fan
filters by loosening
the
wing
nuts on the filter brackets.
3. Position the thennal
scanning
device as needed to
obtain
the
desired
measurements.
Troubleshooting
and Solar Energy Technical Support
570-1001793-0SB