GROUND FAULT INTERRUPT DEVICE
The inve1ter is equipped
with
a ground fault detector intenupter (GFDI). The purpose
of the GFDI is to detect a ground fault (unintended current flow from the
solar
panels
to earth ground) and in this event, disable the inverter.
The GFDI functions using a
3
A fuse to connect
or
bond the
solar
array negative
(or
the
solar
array positive, if using a positively grounded panel atTay) to earth
ground.
If the ground fault
cmTent
exceeds the fuse limit between the grounded array terminal
and the earth ground, the fuse
will
open and disconnect the
solar
panels from their
ground reference, inte1rupting the ground fault. In this
situation,
the inverter will
cease
operation and display a fault message.
To Respond to a Ground Fault
&
WARNING:
For the GFDI circuit to function as designed, the solar array safety ground
must not be connected to the PV array positive or negative leads. Bonding
the safety ground to the grounded leg of the array anywhere but through the
inverter will cause the GFDI circuit to be bypassed. This would defeat the
operation of the GFDI and potentially create an unsafe operating condition.
Lb._
A VERTISSEMENT:
Pour que le circuit GFDI fonctionne normalement, la prise de terre de
securite du systeme PV ne dolt pas etre branche aux cAbles positifs ou
nltgatifs des piles PV. Brancher la prise de terre de securite au pied des piles
ou
a
toute autre partie que l'onduleur causerait une mise hors circuit du
GFDI. Ceci ne empecherait le fonctionnement normale du circuit GFDI et
creerait des conditions de fonctionnement potentiellement dangereuses.
• If the inverter displays
a
ground fault
as shown
in the following figure tmn off
the
AC
and DC to the inverter and refer to the inverter maintenance and
troubleshooting information.
Fault
AC FAST UNDERVOLT A
GROUND FAULT
Figure 5-11.
Ground fault
error message
Related Links
• "Maintenance" on page 7-1
• "Troubleshooting and Solar Energy Technical Support" on page 8-1