System Neutral; Utility Grid Interconnection; Utility Connection Requirements; Contacting Your Local Utility - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced Energy
bus
bar is
located
below
the DC
subpanel compartment
in the front left
of
the inve1ter
cabinet.
The PV
a.nay
is
grounded
internally by means
of
the
GFDI.
The inve1ter is
shipped
preconfigured with positive
or negative
PV
a.nay
grounding
based
on
the preference
specified when
the
order is
placed.
System Neutral
The inve1ter has been
ce1tified
to national
standards
for
installation
without a
neutral
conductor.
Do not
connect a
neutral
conductor
from the
AC service
panel to the
inve1ter.
Lt
WARNING:
The
AC
output/neutral must not be bonded
to
ground within the equipment.
Lt
AVERTISSEMENT:
La
sortie et le neutre CA ne
doivent
pas etre branches
a
la
masse
a
l'interieur du
dispositif.
UTILITY GRID INTERCONNECTION
Utility Connection Requirements
Review
all
applicable national
and
local
codes
for
specific
requirements for the
size
of
the
electrical se1vice and
the amount of
cunent
that
is
allowed to be fed into the
panel by the
inve1
ter.
Contacting Your Local Utility
Before connecting the
inve1ter,
contact your electrical utility
to ensure there are no
local restiictions
or
special
requirements.
Your local utility
company
may require
specific
inspections, equipment,
or other
procedures not
covered
in
this
document.
Voltage Output
3-6
This
inve1ter
is
designed to
be connected
to
a
three
phase, grounded,
wye
ti·ansfo1mer.
The
AC
output
voltage
is listed
on
the
inve1 ter
name
plate
for
the output
voltage wye
configuration. Do not
change
the
output voltage of
the inve1ter.
AC
and
DC
power
requirements are included in the
specifications.