Cooling Specifications - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced
Energy
EFFICIENCY CURVES FOR THE AE 100TX (600 VAC) MODEL
CEC
Efficiency=
96.0%
100
95
I
v
90
*-
~
85
.!I!
0
IE
80
w
-295
75
Vdc
-
-
341
Vdc
70
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
% of Rated Output Power
4669
Figure 9-6.
Efficiency
curves for the AE 100TX (600 VAC) model
Table 9-9. Efficiency
specifications for the AE 100TX (600 VAC) model
Power Level in Percent and kW
Input Voltage
10%
20%
30%
50%
75%
100%
Weighted
(VDC)
10.00
20.00
30.00
50.00
75.00
100.00
VMIN
295
93.8
96.1
96.5
96.6
96.3
95.9
96.26810
VNOM
341
93.2
95.8
96.3
96.4
96.1
95.8
96.06103
VMAX
480
91.5
94.8
95.5
95.8
95.6
95.2
95.38937
COOLING SPECIFICATIONS
Table 9-10.
Cooling specifications
Description
Specification
Cooling method
Forced convection
Maximum
heat
rejection rate
AE 75TX:
14,000
BTU/hr
AE
lOOTX:
18,500
BTU/hr
Maximum fan
air
flow
rate
708
liters
per second (1500 CFM)
A-10
Specifications
570-1001793-058