Advanced Energy AE 75TX Installation And Operation Manual page 41

Table of Contents

Advertisement

Advanced Energy®
AE
?STX and
AE
1
OOTX
Inverters
Table 3-1.
Inverter clearances (Continued)
Location
Sides
Top
Distance
Description
152 mm
(6") each
The minimum
side clearances are
152 mm
(6")
on
one side of
side
or
152 mm
the inve1ter and
914
mm
(36")
on the other side to
allow
( 6
11
)
on one side
access
to
the
external
mounting
flanges. The installer may
with 914mm
select which side
has
clearance. The
9 14
mm
(36") will
(36") on the other
provide future
access to
the magnetics
section
for retorquing
side
bolts
and
the1mal
scans
of
com1ections.
However,
the
914
mm
(36") on
the side
is
not
a NEC
setback requirement. 152
lllln
(6") on
each
side
is
an acceptable
installation practice.
356
mm
(14")
The top clearance
is
required above the air intake hood to
maintain the
filters
and
fans.
Clearances are
shown in the figure
below.
l3~6mm
L
14")
/
AC:
•·
__
LJ
~
.
--
914mm
(36")
Figure
3-
1.
Inverter clearances
152 mm or 914 mm
(6"
or
36")
AE
recommends
that
only one
side,
right or
left,
have the full
914
mm
(36")
clearance while the
other
side
must have 152 mm
(6").
The
above
figure
shows
152
mm
(6")
on
the left with
914
mm
(36") on the
right side. This
allows access
to the
magnetics
section for retorquing bolts
and
the1mal
scan
of
connections. This
is
not a
code
setback
requirement
and
152 mm
(6") on each side
is
an acceptable installation
practice.
570-1001793-0SB
Planning
3-3