Connecting To The Electrical Grid - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced Energy
4-12
considerations
for
ampacity, temperanire,
and conduit.
In
addition,
wire should
be
sized
to minimize
voltage drop.
Install the inve1ter
on a dedicated
branch circuit
with a
recommended
circuit breaker
rating as
specified
in
the
following
table.
Table
4-1.
Branch breaker size recommendations
Model
208 VAC
480VAC
600
VAC
AE
75TX
300A
125
A
lOOA
AE lOOTX
400A
175
A
125A
The
inve1ter
does
not have internal
AC
fusing
so
it
is
impo1
tant to size the branch
circuit
protection
appropiiately.
When
an
inve1
ter is installed
on an
electiical
panel,
the
AC
operating
voltage
range
of the
inve1
ter should be
considered.
Voltages outside this
range
will
cause
the
inve1ter to fault.
See
the unit specifications for
AC
operating
voltage
ranges.
Table
4-2. Operational voltage ranges per electrical panel
Electrical Panel
Operational Voltage Range
208 VAC
183
VAC
to
228 VAC
480VAC
422
VAC
to
528 VAC
600VAC
528
VAC
to
660 VAC
Related Links
"Electrical Specifications"
on page
9-1
CONNECTING TO THE ELECTRICAL GRID
The
inve1ter
is connected
to the electiical
giid
using four
wires:
Phase
A voltage
Phase B
voltage
Phase
C voltage
Ground
Important
Do
NOT connect a
neutral
wire
to
the wye
point
of
the isolation transfonner.
The four
AC
tennination
bus
bars
for
phases
A,
B,
C,
and
gi·ound are
located in the
lower right of the
AC
panel. The
phase bus
bars
are ve1tically
mounted and the
gi·otmd
bus
bar
is
horizontally mounted at the
bottom of the
cabinet. Each
bus bar
has
eight
rows
of
two 3/8"
diameter
holes,
spaced 1" apa1t ve1tically.
Installing
570-1001793-0SB